GB – CapacityTolerance
Compares the capacity declared on the current bill to the capacity declared on the previous bill and fails if it is not within a specified tolerance.
The Validator checks field 1028 (Capacity kVA Value)
The Validator will be unable to complete if there is not a previous bill
Validator Set Up
Variables
Variable | Description |
---|---|
Bill will pass validation if the Query Value is less than (£) | Enter a monitory figure, for example 50. The Validator will only fail if the value of the difference is above £50 |
Tolerance value % | Enter a percentage figure that you want the value to be within, for example enter 1 (for 1%) |
Failure Prompt
Total capacity within % of previous bill: FAILED - The name of the Validator
'tolerance=1.00' - Tolerance set in the Validator - 1%
'capUnits=400.00' - The value entered into field 1028, 400 kVA
'MinimumQueryValue=50.00' - The minimum amount the query needs to be (in £s) for the Validator to fail, ie £50
'upperlimit=191.90' - The amount of the kVA on the previous bill plus 1% (as set in the Validator) 190 + 1.90 (1%) = 191.90
'capcost=200.00' - The value in the Capacity kVA field (field 1028)
'QueryValue=105.00' - The monitory value of the difference in the previous bill kVA and current bill kVA (current bill £200.00, previous bill £95, £200 - £95 = £105).
'lowerlimit=188.10 - The amount of the kVA on the previous bill minus 1% (as set in the Validator) 190 - 1.90 (1%) = 188.10