Sigma Online User Manual
Metering - Clocking Issues
Introduction
'Clocking' is when a meter goes around the clock, ie it gets to a reading of 9999 and then goes back and starts again from 1. It can cause an issue when a reading lower than the previous reading is added. Sigma then calculates high consumption as it assumes it has gone round the clock.
Note, this process is the same for Periodic or Non Periodic Channels that are set to Meter Readings (not Values), ie where incremental Meter Readings are added to the Channel.
Checking the Channel Set Up
The standard set up for a Channel that records Meter Readings is as follows:
- Right click on the Channel > Edit
- Expand the Advanced Measurement Settings section
       Â
Note: If the Clocking Threshold (CTF) is set at 100%, the Meter will always clock when the Present Reading is less than Previous Reading
Channel Editor SettingsÂ
Note: The above Channel is set to Meter Readings and has a Maximum Value added (ie the number of digits in the Meter Reading) and Clocking Threshold of 100%, so Sigma will check if the Meter clocks. Â
     Â
Viewing the Channel DataÂ
In the example below, the reading for 3rd of November is lower than the previous reading, ie has gone from a Reading of 100, round the clock to 99999 (the figure in the Max Value) and then up to 91.
This causes a spike in consumption as Sigma assumes the meter has clocked.
This would show a consumption of 99,981 (as the Maximum Value set in the Channel is 99999)
- From the Channel Editor > click Edit Data
      Â
Date | Reading | Advance |
---|---|---|
31/10/22 | 95 | n/a |
01/11/22 | 100 | 5 |
03/11/22 | 91 | -9 (although Sigma sees this as 100,090) |
05/11/22 | 120 | 29 |
There is a total advance of 25 for the period (because of the negative reading): 120 (Present Meter Reading) - 95 (Start Meter Reading) = 25.
 But the spike in consumption affects the profile (and reporting),Â
Energy Intelligence Report
If you then run a report on the Consumption, it will not be a true reflection.
From Energy Intelligence, run the General Graph and Table for Metered Consumption Report:
The daily consumption shows as 49,995 on 1st and 2nd November, with a total consumption of 100,024
Adjusting the Settings
To overcome the spike, you can lower the Clocking Threshold to 90% (for example).
- Right click on the Channel > Edit
- Set the Clocking Threshold, to 90 (90%)
    Â
With the Clocking Threshold set at 90% (0.9), the reading of 91 on 03/11/22 would be within the acceptable threshold and would treat that as a negative value, not a clocked value, meaning a small dip in consumption, but not a large spike
- 90 (the Clocking Threshold) / 100 (the previous reading) = 0.90  91 present reading) / 100 (previous reading) = 0.91.   0.91 is greater than 90% (.90), The reading on 90 is treated as a negative value, not a clocked value
Re running the Energy Intelligence Report
After changing the sessions (and refreshing Energy Intelligence), rerunning the Report will give the following:
- The daily consumption does show as negative on 1st and 2nd November, but the total consumption for the period is 25 (which is correct)Â - a much better report than if the Clocking Threshold was 100%
    Â
Examples when Clocking Threshold is set to 90%
Present Reading is Higher that the Previous Read
Present Read (120) is more than the Previous Read (91)
- Sigma calculates the consumption: 120 (present read) - 91 (previous read) = 29
- An advance of 29
         Â
Present Reading is Less that the Previous Read, within the Clocking Threshold
Present Reading is 100 and Previous Reading is 91
- Sigma calculates the consumption:Â 100 (present read) - 91 (previous read) = -9 (negative consumption)
- As the consumption appears negative, Sigma checks if it is within the Clocking Threshold
- 90 (Clocking Threshold) / 100 (Previous Meter Reading) = 0.90Â x 100 = 90Â Â Â
- As the difference is -9 (less than 90%) (the clocking threshold)
- Sigma calculates a negative consumption of -9
- As the consumption appears negative, Sigma checks if it is within the Clocking Threshold
               Â
Present Reading is Less that the Previous Read, not within of the Clocking Threshold
Present Reading is 51 and Previous Reading is 120
- Sigma calculates the consumption:Â 120 (present read) - 51Â (previous read) = -61 (negative consumption)
- As the consumption appears negative, Sigma checks if it is within 90% of the Clocking Threshold
- 51 (present reading) / 120 (previous reading) = 0.425.  0.425 is less than .90 (90%), The reading of 51 is treated as a having gone round the clock
- As the difference is more than 90% (the clocking threshold, Sigma calculates a positive consumption of 99,930
- It is assumed that the meter has clocked, so calculates 9999 (Max Value) - 120 (previous reading) + 51 (current reading) = 99,930
                Â
Notes
- Setting the Clocking Threshold to 90% will help with Spikes caused by a negative values here and there, it treats the difference as negative and give an overall better picture
- Setting the Clocking Threshold to 90% will not work for lots of null (missing) reads
- Nulls are treated as zeros (ie the exact meter register clock reading value which will always be less than or equal to the previous read)
- The fractions may vary from 1% to 99% so a 90% clock will not set them as the desired credits so you need to Interpolated filling first.
- Fill the null zero missing reads with smoothed calculated values in order to remove the nulls. Then apply the clocking value
Updating the Channels in bulk
Setting the Clocking Threshold and Maximum Value can be done using the Data Edit Spreadsheet Activity:
- Open the Data Edit Spreadsheet Activity
- Highlight the required Non Periodic Channels > Click Edit Items
- Tick the following fields on the Non Periodic Channel Tab
- Name
- Meter Readings
- Minimum Value
- Maximum Value
- Clocking Threshold
- Max is Last
- Tick the following from the References Tab (optional)
- Site and Commodity (if required)
- Click Edit Fields
    Â
Setting the Channel to Meter Readings
- Tick to record the values in the Channel as Meter Readings (incremental), not Values
- Tip:Â To tick all, click on the small white downward arrow on the Column Header > Check All
Setting the Maximum Value
- Add a value to Maximum Value column, ie 99999 (the figure at which the Meter will clock and start back at zero)
- Note:Â This will automatically untick any Minimum or Maximum Values
Adding the Clocking Threshold
- Change the Clocking Threshold to your requirement, for example 90
Note: These can be done in bulk by exporting the data, amending and reimporting. Click here for more information.Â
- Click Save to save the changes
@ Copyright TEAM - Energy Auditing Agency Limited Registered Number 1916768 Website: www.teamenergy.com Telephone: +44 (0)1908 690018